High Voltage Shielded Cable for Lightning Arrester

Product Details:
Arrester Type Station Type, Intermediate Type, Distribution TypeWe are involved in the domain of manufacture High Voltage Shielded Cable for Lightning Arrester which is designed to convey lightning energy to ground with minimal risk of “side flashing” or structure electrification. The need to reduce “side flashing” and structure electrification protects both personnel and sensitive electronic equipment from the devastating risks of a lightning strike.




Specifications:
Concentric Conductor Nominal cross sectional area 90mm²
Sheath Thickness (Nominal) 3.00mm
Overall Diameter (Approx) 37mm
Weight of Cable 2.050 kg per metre
DC Resistance of conductor at 20ºC (Max) Ohm/km 0.387
DC Resistance of screen at 20ºC (Max) Ohm/km 0.448
Insulation resistance at 20ºC (Min) M Ohm-km 1,830
Thermal Short circuit current (1 second) KA 7.15